automating all operations of the incinerator

automating all operations of the incinerator Construction Constructed from heavy duty mild or aluminized steel or equal and approved equivalent
Insulation Refractory material lining
Combustion Temperatures   Above 850 0C, controlled electronically
Gas residue or retention time                                           > 2 second at minimum 850 0C
Secondary Burner Provided, 
Diesel fired,                                                                      
Fully automatic, with fuel, temperature and speed controls 
With ignition system
Flame detector

Air fan       
Complete with safety features, flame failure
Diesel fired fuel injector type
Flange mounted
Ejector Provided, Venturi type, for cooling the flue gases
Combustion Air Fan                   Provided for supplying combustion and creating a
negative drift and turbulences with variable speed control
Temperature Maximum  1600 0C       
3.4       Chimney              
Construction Constructed from heavy duty mild or aluminized steel  or equal and approved equivalent
Refractory material lining
Length 10 m above ground
Bore about 350mm diameter
Discharge temperatures          About 850 0C
Emissions To comply with standards in section 9 of third schedule of the waste management regulations, 2006.
    3.5       Electrical System   
Control unit                                        Fully automatic with microprocessor based control
unit (PLC) automating all operations of the incinerator
Capable of monitoring all incinerator parameters
With large LCD or similar for display of all progress
Parameters  i.e. temperature of primary and second chambers , turbulence and time
With status lamp
With user of defined and differed programmed operating cycles for different type of loads/conditions
With safety interlocks, display of errors and visible and audio alarms.
System for continuous  emission monitoring